GEA AWP GmbH Armaturenstr. 2 17291 Prenzlau Germany

Self-Regulating valve for optimized condensation conditions.

HSX High Pressure Float Valve

HSX high pressure float valves have a shut-off valve welded onto the inlet as well as onto the outlet, as well as a vacuum nozzle and an externally operated transport lock / manual adjustment that can be operated from the outside. In addition, service valves for emptying and discharging non-condensable gases can be installed via two G¼” threaded connections. Depending on the intended regulation values, the size of the outlet aperture is mechanically opened by means of a float operated valve. The condensed refrigerant is released from the high-pressure side to the low-pressure side and returned to the reservoir. The transport lock must be “released” before use; this mechanical design operates without electrical power and regular maintenance intervals are not required. When ordering: – Please specify the intended regulation aperture (-X, -H, -M, -L), the refrigerant type and the application (Qo, to ,tc).

Technical Features

Technical Specification

Material

steel

Nominal Size

DN 50 and DN 80

Nominal Pressure Level

PS 40

Temperature Range for Standard Valves

-60 °C to +75 °C

Connections

butt welding ends as per DIN and ANSI

Additional Information

integrated manual adjustment / transport lock

Where to find us