GEA AWP GmbH Armaturenstr. 2 17291 Prenzlau Germany

Dual safety valves consisting of one 3-way valve in compact design, made of aluminum and two safety valves dependent or independent on back pressure.

WVR AL SVA / SVU Dual Safety Valves

AWP dual safety valves are designed to be used as relief or overflow valves in the refrigerant cycles of industrial refrigeration systems. They are available with safety valves either back pressure dependent or independent to protect the refrigeration systems and their components from excess pressure (see also EN 378 part 2). They comply with AD2000 regulations. After their initial response AWP safety valves open within 10 % of pressure increase up to the designed limitation. They close within a pressure drop of 10 % below the response pressure. The 3-way valve enables easy checks and maintenances of the safety valves without the system’s operation to be interrupted. One of the two outlet nozzles is always open whereas the other one is closed. So one safety valve can be checked or removed while the other one remains in service to protect the system. The compact design of the WVR AL requires minimum space and enables horizontal and vertical assembly. Compared to steel and stainless steel valve types the weight could be reduced by up to 30 % by using salt-water resistant aluminium EN AW-6082 as body material.

Technical Features

Technical Specification

Material

aluminum (3-way valve)
steel or stainless steel (safety valves)

Nominal Size

DN 15-32

Nominal Pressure Level

PS 25, PS 40, PS 63

Temperature Range for Standard Valves

WVR AL-SVAA / WVR AL-SVUA: -60 °C to +120 °C
WVR AL-SVAB / WVR AL SVUB: -50 °C to +110 °C

Connections

flanged ends as per DIN and ANSI

Additional Information

available with bursting discs, bursting disc holder and excess flow valve